Description: With characteristics of high
fire extinguishing efficiency, no pollution, non conducting, low toxicity, small
storage space, excellent environmental protection performance, etc, seven fluorine propane
fire extinguishing agent is a kind of clean
gas extinguishing agent that application technique is comparatively mature
and all items of performance index are comparatively ideal,
and seven fluorine propane
fire extinguishing system has been widely applied in China
and other nations
and areas in the world.
Scope of application: it can put out
electrical fire, liquid fire, melted solid fire, solid surface
fire and can cut off
gas fire of
air source before
fire extinguishing.
Field of application: the places where valuable, priceless treasure
and precious data
and archives are put; facilities that can be damaged by
water stain; places where people are often there; places where residuum is difficult to clean after
fire extinguishing agent is sprayed; place that has comparatively small
storage bottle space
and need less
fire extinguishing agent
and high
fire extinguishing efficiency; places that protected objects are
electric equipments
and must use non conductive
fire extinguishing agent;
Typical protective area:
Date processing center, telegraphic communication, airport control center, expensive
medical facilities, bank treasury, expensive industrial equipment, library, museum, robot, clean room, anechoic chamber, emergency
power facilities,
computer room
and inflammable liquid
storage area.
System composition: system is composed of the
fire automatic
alarm control system
and fixed
fire extinguishing equipment; fixed
fire extinguishing
equipment is composed of
storage bottle set of
fire extinguishing agent, starting bottle, selector valve, one-way valve, high-pressure hose,
safety valve, pressure relay, nozzle,
steel cylinder framework,
pipe network system, etc.
System control mode: automatic, manual, emergency starting
Main technical parameters:
Mode of
fire extinguishing technology: total flooding;
pressure of starting bottle: 7.50.5 MPa;
Storage temperature: -10~50;
Spraying time: 10s 2
Working pressure of system design: 2.5MPa ;4.2 MPa;
single protection area: 500m
Minimum
design concentration of system
fire extinguishing: 7%;
single protection volume: 2000m3
Filling density: 1150 kg/m3
starting
power supply: 24V; 1.2A
Working pressure of nozzle: generally 0.8 MPa; volume of reservoir vessel: 40~100L